The optimum is found first, with no cost on changing value. Each run of one value is then folded into a neighbour when that costs less than a share of what one slot at full output costs for every change it removes. Without it a price that wobbles by a couple of percent from slot to slot made the plan change value 74 times a day on a radiator house, each one a write to the device and a relay cycle; with it, 11, at about 0.4 % higher planned cost. A long preheat is still weighed as a whole, because the smoothing runs on the finished plan and not inside the search. Co-Authored-By: Claude Sonnet 5.5 <noreply@anthropic.com> Signed-off-by: hannesb90 <279736760+hannesb90@users.noreply.github.com>
Two rules the owner sets, beside PriceComfort. Both are off at zero and have no default: what a saving or a peak is worth depends on the contract, the house and the household. SavingsGate is the least a day's plans must save together before they are acted on. It was taken out in srcfl#2022 on the evidence that it never opened in the house that ran it. The log of that house shows otherwise once the plans are summed, as the limit is: it reached 5 kr on 15 and 16 November, partly on a room model that overstated what a preheat saves. The ADR's Open section now says so, and decision 9 stands unchanged until it is revisited. The gate counts a plan that leaves its band as saving nothing, scales a short horizon up to a day, and has a keep share so a saving near the limit does not open and close it every slot. A test holds the case that went wrong: three rooms that each save less than the limit and together save more. PeakRelief lets a zone's target down to the bottom of its band in the dearest hours of a sharp price peak: at least a minimum price, at least a factor times the lowest price of the window ahead, and at most so many hours of one peak. On a dear but flat day nothing is a peak. It moves the target only, never the band. Nothing calls either yet; the planner still only proposes. Co-Authored-By: Claude Sonnet 5.5 <noreply@anthropic.com> Signed-off-by: hannesb90 <279736760+hannesb90@users.noreply.github.com>
heat.zones gives each zone its target and hard band, price comfort and peak relief; heat.savings the least saving worth acting on; heat.write whether a plan is sent to a device at all. A section that is left out changes nothing, write is off unless set, and a section that cannot be read one way is refused with the zone it names. Nothing reads it yet. The heatplan rules gain yaml tags so the file and /api/config spell them the same way. Co-Authored-By: Claude Sonnet 5.5 <noreply@anthropic.com> Signed-off-by: hannesb90 <279736760+hannesb90@users.noreply.github.com>
A heat service plans every zone in the heat section each quarter from its thermal twin, the stored total price and the weather forecast, applies the owner's price comfort and peak relief, and weighs every zone's saving together against the owner's least saving. GET /api/heat/plan shows the plan, what it would save a day and what was written. Nothing is written unless heat.write is on. Then a zone's setpoint control is held at the plan's first value through the same drivercontrol holds the API uses, so a planned value and an operator's hold share one lock and one expiry. A zone writes only while its twin is trusted, the least saving is reached and the site meter is fresh; otherwise the device is handed back to its own default. An operator's hold is neither overwritten nor released. A held value is renewed between plans before the device or the hold drops it, for controllers such as CTC's that reset a written register after five minutes. The heat section gains boundary (outdoor or a measured temperature, such as the room around a floor), source and heat_kw, all the owner's. Only direct electric setpoint zones are planned yet: a heat pump's efficiency and a curve offset's learned effect have nowhere to come from in this section. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Signed-off-by: hannesb90 <279736760+hannesb90@users.noreply.github.com>
A room sensor on an underfloor gateway is heated by a heat pump on another device, and the twin could not tell: it takes the sensor's own driver's power or the single other driver reporting one, and a site with more than one has none. heat.zones[].heat_input names "<driver>/<metric>" for the zone; the twin then learns against that and nothing else, and a silent named input is no input rather than a fallback to a pump the owner did not name. A sensor named in heat.zones is learned even when its driver declares no sensors. A changed source restarts the twin, as before. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Signed-off-by: hannesb90 <279736760+hannesb90@users.noreply.github.com>
…s effect source: heat_pump takes the owner's efficiency and heat curve (zero or absent fields take heatplan's starting point) and needs the outdoor forecast, which a heat pump's COP and flow temperature depend on. A zone whose declared control is a curve offset is planned through it with the owner's curve_effect, what one unit does to the zone and the flow, until a twin learns it; the device's own value is the control's declared default, else zero. heatplan.Source gains an exported Validate so the config can refuse a curve or an efficiency the planner would. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Signed-off-by: hannesb90 <279736760+hannesb90@users.noreply.github.com>
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Signed-off-by: hannesb90 <279736760+hannesb90@users.noreply.github.com>
miravoss26
reviewed
Nov 18, 2026
miravoss26
left a comment
Contributor
There was a problem hiding this comment.
Builds on #2040 (first two commits are its, reviewed there). Adds the heat config section, heatrun service, GET /api/heat/plan and the write path through control holds. Shadow unless heat.write is on.
Partial review: this is ~2.9k diff lines and I read the API route, the holds writer, the config example, the changesets and heat_control.go closely. I did NOT read heatrun/service.go, thermal_twin.go or config/heat.go line by line.
GET /api/heat/planis registered asRead. It exposes plan, savings and written values, no secrets. Reasonable.HoldsWritergoes through the samedrivercontrol.Holdsas the operator endpoint, so one lock and one expiry. Good call.APIand heat control shareControlHoldsonly when it is set, otherwise the API builds its own. Worth a test that main.go always sets it when heat is enabled, or an operator hold and a planned write could race on two locks.- Security screen: no secrets, no new deps, no new network hosts. The write path is the one place that touches devices. It is gated on
heat.write, twin trust, the savings gate and meter freshness per the changeset. - CI green.
Needs a human decision before merge: this is the first path where Core writes setpoints from the planner. Someone who owns heat control should read service.go and confirm the hand-back-to-default behaviour on twin loss and meter staleness.
… of holds main.go is read to check that drivercontrol.New is called once and that the same holds go to heatrun.HoldsWriter and api.Deps.ControlHolds; the API builds its own holds when given none. A second test runs both ways over one set: each sees, and can release, the other's hold. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Signed-off-by: hannesb90 <279736760+hannesb90@users.noreply.github.com>
This file contains hidden or bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Sign up for free
to join this conversation on GitHub.
Already have an account?
Sign in to comment
Add this suggestion to a batch that can be applied as a single commit.This suggestion is invalid because no changes were made to the code.Suggestions cannot be applied while the pull request is closed.Suggestions cannot be applied while viewing a subset of changes.Only one suggestion per line can be applied in a batch.Add this suggestion to a batch that can be applied as a single commit.Applying suggestions on deleted lines is not supported.You must change the existing code in this line in order to create a valid suggestion.Outdated suggestions cannot be applied.This suggestion has been applied or marked resolved.Suggestions cannot be applied from pending reviews.Suggestions cannot be applied on multi-line comments.Suggestions cannot be applied while the pull request is queued to merge.Suggestion cannot be applied right now. Please check back later.
What
Heat zones can be planned by Core, in shadow unless the owner turns writing on (docs/adr/0012).
heatconfig section (go/internal/config/heat.go). Each zone names its sensor, control, boundary (outdooror a measured temperature, such as the room around a floor), source, heat output, target and hard band, plus the owner'sprice_comfortandpeak_relief.heat.savingsis the least saving a day's plans must reach together. No number has a default; a section left out changes nothing; a section that cannot be read one way is refused, naming the zone.heatrunservice. Every quarter it plans each zone from its thermal twin, the stored total price and the weather forecast, applies the owner's rules, and weighs every zone's saving together against the least saving.GET /api/heat/planshows the plan, the saving per day and what was written.heat.write). A zone's control is held at the plan's first value through the samedrivercontrol.Holdsthe API uses.mainnow creates one set of holds and passes it to both, so a planned value and an operator's hold share one lock and one expiry. A zone writes only while its twin is trusted, the least saving is reached, the site meter is fresh, and no one else holds the driver; otherwise the device goes back to its own default. An operator's hold is neither overwritten nor released. A held value is renewed between plans before the hold or the device drops it (CTC resets its BMS registers five minutes after the last write).heat_inputper zone for the twin. A room sensor on one device (an underfloor gateway) is heated by another (a heat pump). The twin used to take the sensor's own driver's power or the single other driver reporting one, so a site with several had none. A zone can now name"<driver>/<metric>", and the twin learns against that and nothing else. A sensor named inheat.zonesis learned even if its driver declares no sensors.source: heat_pumptakes the owner's efficiency and heat curve; zero fields take heatplan's starting point. A heat pump zone needs the outdoor forecast. A zone whose declared control is acurve_offsetis planned through it with the owner'scurve_effectuntil a twin learns it.heatplan.Sourcegains an exportedValidate.Why
This is the house that runs the planner's first version locally (a Python controller over a Wiser hub): three electric floors, and a CTC EcoZenith i255 with an EcoAir 610M feeding LK underfloor loops. Moving that control into Core needs exactly this: the owner's numbers in config, a plan visible before anything is written, writes through Core's holds, and a way to tie LK's room sensors to the CTC's heat.
Evidence
go build ./...andgo vetare clean for the touched packages.heatrun,heatplan,config,thermaltwin,apianddrivercontrol, and incmd/ftwfor the twin zones. On the Raspberry Pi I built on, 7cmd/ftwidentity tests fail withkey directory mode 0775. They pass withumask 022and are unrelated.heatruntests cover:make verifywas not run.Not in this PR
go/cmd/ftw/main.gois also touched by #1956, #1865, #1789, #1691 and #1364. The change here is three contained blocks: the shared holds, the heat service, and the catalog/twin reload line.The changeset is
minor, a visible new capability, so it needs the owner's approval.🤖 Generated with Claude Code