## [Unreleased]

### ctc_ecozenith 0.1.0

New read-only driver for the CTC EcoZenith i250/i255 controller over Modbus
TCP (CTC's BMS register list). It reports outdoor, flow, flow setpoint, return, radiator,
heat-pump in/out and hot-water temperatures, compressor speed and status,
immersion heater power, and the heat curve's room setting, inclination and
adjustment. A room temperature is reported only when a room sensor is fitted.
The controller has no register for the compressor's electrical input, so the
driver reports no `hp_power_w`.

The controller does not answer an address it lacks; the request just times
out. The driver therefore reads only registers CTC lists for the i250. One
that stops answering for three polls is retried less and less often, at most
every 10 minutes, and never given up for good: the controller also refuses
reads while another client holds its connection.

### easee_cloud 1.4.1

The driver says its session energy is coarse, with `session_wh_coarse`. Easee
Expand Down
2 changes: 2 additions & 0 deletions SUPPORT_STATUS.md
Original file line number Diff line number Diff line change
Expand Up @@ -34,6 +34,8 @@ Catalog source is not proof that a target can install or run a driver.
| chint | 1.0.5 | blixt-l1 | not_assessed | — | not_recorded | not_assessed |
| circutor | 1.0.5 | ftw-core | not_assessed | — | not_recorded | not_assessed |
| circutor | 1.0.5 | blixt-l1 | not_assessed | — | not_recorded | not_assessed |
| ctc_ecozenith | 0.1.0 | ftw-core | not_assessed | — | not_recorded | not_assessed |
| ctc_ecozenith | 0.1.0 | blixt-l1 | not_assessed | — | not_recorded | not_assessed |
| ctek | 0.3.3 | ftw-core | not_assessed | — | not_recorded | not_assessed |
| ctek | 0.3.3 | blixt-l1 | not_assessed | — | not_recorded | not_assessed |
| ctek_hybrid | 0.3.2 | ftw-core | not_assessed | — | not_recorded | not_assessed |
Expand Down
13 changes: 13 additions & 0 deletions devices.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -175,6 +175,19 @@ manufacturers:
control: true
firmware_versions: ""
notes: ""
- name: "CTC"
model_families:
- name: "EcoZenith i250/i255"
variants: [EcoZenith i255]
regions: [SE]
protocols:
- protocol: modbus
driver: "ctc_ecozenith"
version: "0.1.0"
ders: [heatpump]
control: false
firmware_versions: "display 2024-07-19"
notes: "Read-only heat-pump telemetry over Modbus TCP (BMS), function code 3, register numbers as listed by CTC. The controller does not answer an address it lacks, so only documented i250 registers are read. Reports no compressor electrical power."
- name: "CTEK"
model_families:
- name: "CTEK Chargestorm (API v1)"
Expand Down
323 changes: 323 additions & 0 deletions drivers/lua/ctc_ecozenith.lua
Original file line number Diff line number Diff line change
@@ -0,0 +1,323 @@
-- CTC EcoZenith i250/i255 heat pump controller — Modbus TCP, read-only.
--
-- Emits: metrics only, via host.emit_metric. A heat pump is a load, and this
-- driver never emits a meter, so it does no sign conversion and cannot
-- double-count against the site's grid meter.
-- Control: none. New drivers start read-only. The 1000-series registers
-- CTC documents for control are listed at the end of this file so the next
-- step does not have to rediscover them.
--
-- SOURCE
-- CTC "BMS via TCP/IP" register list, Swedish and English editions, the
-- manifest's upstream_docs. Read with function code 3 (holding), offset 0:
-- the register number in the list is the address on the wire, no -1.
-- Every value is a signed 16-bit integer; the list gives each one's factor
-- (0.1 for temperatures, kW and RPS; 1 for codes).
--
-- The list has one column per controller family. A register is read here
-- only when the EcoZenith i250 column is marked; the i255 is that
-- controller's successor and the list names it explicitly in its
-- control-register notes.
--
-- WHAT THE DEVICE DOES THAT THE LIST DOES NOT SAY
-- Measured on an EcoZenith i255, display software 2024-07-19, on
-- 2026-11-10:
-- - A request for an address the controller does not have gets NO reply:
-- no Modbus exception, the request just times out, and the next
-- connection may be reset. That is why every read here is a documented
-- i250 register, and why each one is bounded by probe_read below.
-- - A documented register whose sensor is not fitted answers 0, not an
-- error. Room temperature 1 (62203) read 0 on a pump with no room
-- sensor; an unconnected sensor elsewhere read -999.9. Both are treated
-- as absent for the temperatures where 0 cannot be a real reading.
-- - One open connection served 18 reads in 0.16 s. It is a normal Modbus
-- TCP server once it is only asked about registers it has.
-- - It serves one client at a time. While FTW held its connection on
-- 2026-11-11, a second client was reset on its first request, every
-- time. Another BMS, a phone app over Modbus or a test script therefore
-- makes FTW's reads fail for as long as it is connected; see the back-off
-- in probe_read.
--
-- WHAT THE TEMPERATURES ARE, CHECKED AGAINST THE DISPLAY (2026-11-11)
-- - 62011 "Heating system 1: Primary flow" is the flow to the heating
-- system after the mixing valve: hp_flow_temp_c. The display showed
-- 23 °C flow with setpoint 24 °C, and 62007 "Heating system 1:
-- Temperature setpoint primary flow" read 24.0: hp_flow_setpoint_c.
-- - 62006 "Radiator Water" is not that flow. It is the tank water the
-- mixing valve draws from, shown on the display as radiator water 35 °C
-- with setpoint 35 °C while the flow was 23-25 °C. Its setpoint matched
-- the lower tank setpoint (62274). hp_radiator_temp_c keeps CTC's name.
--
-- POWER
-- The controller does not report the compressor's electrical input. The
-- current registers (62171-62173) are the house's incoming phases, read
-- from the controller's own current transformers when they are fitted,
-- not the pump's draw, and they read 0 when they are not. So this driver
-- emits no hp_power_w. Inventing one from RPS would be a guess.
--
-- SETUP ON THE PUMP
-- Display menu Installer/Define/Remote control: define "Modbus TCP". CTC
-- says only displays with three connection ports can do BMS over TCP/IP.
--
-- Config example (config.yaml):
-- drivers:
-- - name: ctc
-- lua: drivers/ctc_ecozenith.lua
-- capabilities:
-- modbus:
-- host: <pump-ip>
-- port: 502
-- unit_id: 1

PROTOCOL = "modbus"

DRIVER = {
host_api_min = 1,
host_api_max = 1,
id = "ctc_ecozenith",
name = "CTC EcoZenith i250/i255",
manufacturer = "CTC",
version = "0.1.0",
protocols = { "modbus" },
capabilities = { "heatpump" },
read_only = true,
description = "CTC EcoZenith i250/i255 heat pump controller via Modbus TCP (BMS). Read-only: temperatures, compressor speed and status, immersion heater power, heat curve settings.",
homepage = "https://www.ctc.se",
authors = { "hannesb90", "Claude (Anthropic)" },
tested_models = { "EcoZenith i255" },
verification_status = "experimental",
verification_notes = "Register reads checked against one EcoZenith i255 (display software 2024-07-19) over Modbus TCP on 2026-11-10. Not yet run as an FTW driver on that pump.",
connection_defaults = {
port = 502,
unit_id = 1,
},
}

-- Registers, as numbered in CTC's list. Each is in the i250 column.
local REG_BLOCK_START = 62000 -- 62000..62015 in one read
local BLOCK_COUNT = 16
local REG_OUTDOOR = 62000 -- Outdoor temperature, 0.1 °C
local REG_STATUS = 62005 -- Status code, see STATUS below
local REG_RADIATOR = 62006 -- Radiator water, 0.1 °C
local REG_HS1_FLOW_SET = 62007 -- Heating system 1: primary flow setpoint, 0.1 °C
local REG_HS1_FLOW = 62011 -- Heating system 1: primary flow, 0.1 °C
local REG_RETURN = 62015 -- Return temp, 0.1 °C
local REG_HP1_STATUS = 62017 -- Heat pump 1 (A1) status code
local REG_HP1_IN = 62027 -- Heat pump 1 (A1) HP in, 0.1 °C
local REG_HP1_OUT = 62037 -- Heat pump 1 (A1) HP out, 0.1 °C
local REG_HP1_SW = 62157 -- Heat pump 1 (A1) software version
local REG_IMMERSION = 62168 -- 62168 upper, 62169 lower: 0.1 kW
local REG_HP1_RPS = 62193 -- Heat pump 1 (A1) current RPS, 0.1
local REG_ROOM1 = 62203 -- Current room temp 1, 0.1 °C
local REG_DISPLAY_SW = 62244 -- 62244 month*100+day, 62245 year
local REG_PRODUCT_TYPE = 62253 -- Product type code
local REG_LOWER_TANK_SET = 62274 -- Lower tank setpoint, 0.1 °C
-- 62275 (DHW lower) sits between these two but is not in the i250 column,
-- so the two are read singly: a controller without it would not answer a
-- read that spans it, and the DHW top temperature would go with it.
local REG_HW_TOP = 62276 -- DHW top temperature, 0.1 °C
local REG_HS1_ROOM_SET = 61509 -- Heating system 1: room setting, 0.1 °C
local REG_HS1_INCLINE = 61513 -- Heating system 1: curve inclination, 0.1
local REG_HS1_ADJUST = 61517 -- Room 1: curve adjustment, 0.1 °C

-- An unconnected sensor. CTC uses -999.9 for it.
local SENSOR_OPEN = -9990

local POLL_MS = 30000

-------------------------------------------------------------------------------
-- Bounded reads. A register that does not answer three polls in a row is
-- backed off: skipped for 1, 2, 4 ... polls, at most MAX_SKIP_POLLS, then
-- tried again. On this controller a missing register costs a full timeout,
-- so paying it every poll would be an outage arriving slowly. It is never
-- given up for good: the controller also refuses reads for a while when
-- another client holds its connection, and a driver that gave up then stayed
-- offline until restart although the pump was answering again.
-------------------------------------------------------------------------------

local BACK_OFF_AFTER = 3
local MAX_SKIP_POLLS = 20 -- 10 min at POLL_MS
local read_failures = {}
local skip_until = {}
local poll_no = 0

local function probe_read(addr, count)
if skip_until[addr] and poll_no < skip_until[addr] then return nil end
local ok, regs = pcall(host.modbus_read, addr, count, "holding")
if ok and regs then
for i = 1, count do
if regs[i] == nil then ok = false break end
end
end
if ok and regs then
if (read_failures[addr] or 0) >= BACK_OFF_AFTER then
host.log("info", string.format("CTC: register %d answers again", addr))
end
read_failures[addr] = nil
skip_until[addr] = nil
return regs
end
local failures = (read_failures[addr] or 0) + 1
read_failures[addr] = failures
if failures >= BACK_OFF_AFTER then
local wait = math.min(1 << (failures - BACK_OFF_AFTER), MAX_SKIP_POLLS)
skip_until[addr] = poll_no + 1 + wait
if failures == BACK_OFF_AFTER then
host.log("info", string.format(
"CTC: register %d did not answer %d times; retrying less " ..
"often, at most every %d polls", addr, BACK_OFF_AFTER, MAX_SKIP_POLLS))
end
end
return nil
end

local function s16(raw)
if raw == nil then return nil end
return host.decode_i16(raw)
end

-- A temperature in 0.1 °C, or nil when the sensor is open.
local function temp(raw)
local v = s16(raw)
if v == nil or v <= SENSOR_OPEN then return nil end
return v / 10
end

-- The same, for a sensor that reads exactly 0 when it is not fitted. Only
-- for places where 0.0 °C is not a real reading in operation: a room, a
-- hot-water tank.
local function fitted_temp(raw)
local v = s16(raw)
if v == nil or v == 0 then return nil end
return temp(raw)
end

local function emit(name, value, unit)
if value ~= nil then host.emit_metric(name, value, unit) end
end

-------------------------------------------------------------------------------
-- Identity, read once and bounded.
-------------------------------------------------------------------------------

local identity_tries = 0
local identity_done = false
local IDENTITY_ATTEMPTS = 3

local function read_identity()
if identity_done or identity_tries >= IDENTITY_ATTEMPTS then return end
identity_tries = identity_tries + 1
local product = probe_read(REG_PRODUCT_TYPE, 1)
local sw = probe_read(REG_DISPLAY_SW, 2)
local hp_sw = probe_read(REG_HP1_SW, 1)
if product then
-- CTC's list gives no table for this code; it is reported as the
-- number so two controllers can at least be told apart.
host.set_model(string.format("EcoZenith (product type %d)", product[1]))
emit("hp_ctc_product_type", product[1], "")
end
if sw then
local md, year = sw[1], sw[2]
host.log("info", string.format("CTC: display software %04d-%02d-%02d",
year, math.floor(md / 100), md % 100))
end
if hp_sw then
emit("hp_ctc_hp1_software", hp_sw[1], "")
end
identity_done = product ~= nil
end

-------------------------------------------------------------------------------
-- Entry points
-------------------------------------------------------------------------------

function driver_init(config)
host.set_make("CTC")
end

function driver_poll()
poll_no = poll_no + 1
read_identity()

local block = probe_read(REG_BLOCK_START, BLOCK_COUNT)
if block then
local function at(reg) return block[reg - REG_BLOCK_START + 1] end
-- Outdoor 0.0 °C is a real reading, so only the open-sensor value
-- counts as absent here.
emit("hp_outdoor_temp_c", temp(at(REG_OUTDOOR)), "°C")
emit("hp_ctc_status", s16(at(REG_STATUS)), "")
emit("hp_radiator_temp_c", temp(at(REG_RADIATOR)), "°C")
emit("hp_flow_temp_c", temp(at(REG_HS1_FLOW)), "°C")
emit("hp_flow_setpoint_c", temp(at(REG_HS1_FLOW_SET)), "°C")
emit("hp_return_temp_c", temp(at(REG_RETURN)), "°C")
end

local hp_status = probe_read(REG_HP1_STATUS, 1)
if hp_status then emit("hp_ctc_compressor_status", s16(hp_status[1]), "") end

local hp_in = probe_read(REG_HP1_IN, 1)
if hp_in then emit("hp_inlet_temp_c", temp(hp_in[1]), "°C") end

local hp_out = probe_read(REG_HP1_OUT, 1)
if hp_out then emit("hp_outlet_temp_c", temp(hp_out[1]), "°C") end

local rps = probe_read(REG_HP1_RPS, 1)
if rps then emit("hp_compressor_rps", s16(rps[1]) / 10, "rps") end

-- The controller reports kW; the host contract is W.
local immersion = probe_read(REG_IMMERSION, 2)
if immersion then
emit("hp_immersion_upper_w", s16(immersion[1]) * 100, "W")
emit("hp_immersion_lower_w", s16(immersion[2]) * 100, "W")
end

local room = probe_read(REG_ROOM1, 1)
if room then emit("hp_indoor_temp_c", fitted_temp(room[1]), "°C") end

local lower_set = probe_read(REG_LOWER_TANK_SET, 1)
if lower_set then emit("hp_lower_tank_setpoint_c", fitted_temp(lower_set[1]), "°C") end

local hw_top = probe_read(REG_HW_TOP, 1)
if hw_top then emit("hp_hw_top_temp_c", fitted_temp(hw_top[1]), "°C") end

local room_set = probe_read(REG_HS1_ROOM_SET, 1)
if room_set then emit("hp_room_setpoint_c", temp(room_set[1]), "°C") end

local incline = probe_read(REG_HS1_INCLINE, 1)
if incline then emit("hp_curve_inclination", s16(incline[1]) / 10, "") end

local adjust = probe_read(REG_HS1_ADJUST, 1)
if adjust then emit("hp_curve_adjustment_c", s16(adjust[1]) / 10, "°C") end

-- hp_poll_ok follows the 16-register block only, on purpose: it holds the
-- status and the main temperatures. While that block is backed off it
-- stays 0, even if the single reads still answer, so a pump that lost
-- its main block does not look healthy.
host.emit_metric("hp_poll_ok", block and 1 or 0, "")
return POLL_MS
end

function driver_cleanup()
end

-- Not used by this read-only driver. Kept as the map for the control step.
--
-- CTC's 1000-series registers are written with function code 16 and "must
-- be updated every 5 minutes, otherwise they are reset", and they also reset
-- on restart. The controller itself therefore hands the device back within
-- five minutes of the last write: a device-side hold, declared later as
-- device_hold_max_s = 300 (docs/adr/0012 in srcfl/ftw).
-- 1005 ElPriceMode, 1 low, 2 normal, 3 high
-- 1006 Extra DHW
-- 1007 DHW mode, 0 economy, 1 normal, 2 comfort
-- 1010 Setpoint heat HC1
-- 1023 Setpoint offset heat HC1
-- 1029 Setpoint flow temp HC1
-- All are in the i250 column. None has been written to a pump yet.
--
-- The settings registers are writable too, and keep their value like a
-- change on the display. On 2026-11-11 61517 (room 1 curve adjustment,
-- factor 0.1) was written on an i255 with function code 16 from -30 to 30
-- (-3.0 to +3.0 °C), with FTW's driver paused because of the one-client
-- limit above. 61517 read back 30 and the flow setpoint 62007 went from
-- 24.0 to 30.0 °C at 4 °C outdoor: the adjustment moves the curve 1:1.